This straightforward scrap removal application called for a high-efficiency backward curved fan with a premium efficiency motor using an Arrangement 1 V-belt drive and a unitary base.
Scrap removal and dust collection are essential in metal or other material recycling, recovery, and refining processes like this one, where fibrous dust and particles can be hazardous byproducts and interrupt production
The backward-curved dust collector fan is installed on the clean-air side of dust collector system, pulling the air and particulates through the filters. The backward curved blades and high-quality welding are key design features to increase the fan’s reliability at higher static pressures and in continuous operations.
Performance: 20,000 cfm airflow @ 11” wg static pressure @ 0.075 lb/ft^3 inlet air density
Product Type | BCHS (backward curved) |
Size | 365 (36.5” diameter wheel) |
Class | 4 |
Arrangement | 1 (belt drive with unitary base) |
Horsepower | 60 HP |
Max Design Temperature | 150°F |
If you have a custom project, contact an application engineer to discuss it in more detail.